Product photo
Industrial UPS 10KVA-200KVA

Industrial UPS 10KVA-200KVA

HQ33i Series · Industrial UPS for critical loads · Input: 3P3W (3P4W) · Output: 1P2W or 3P3W (3P4W) · DC input options available.

Model: HQ33i Series (10kVA–200kVA)
Capacity
10kVA–200kVA
Architecture
Output isolated low-frequency transformer · IGBT rectifier with PFC · Full-bridge IGBT inverter
Input
3P3W (3P4W) · AC 380/400/415/480V · Voltage range ±25% · 50/60Hz ±10%
Output
1P2W or 3P3W (3P4W) · 220/230/240/277V or 380/400/415/480V · Voltage regulation ±1%
Parameter Value
SeriesHQ33i
Capacity range10kVA–200kVA (ratings include 10 / 20 / 30 / 40 / 50 / 60 / 80 / 100 / 120 / 160 / 200kVA)
Input phase3P3W (3P4W)
Input voltageAC 380V / 400V / 415V / 480V (other specifications available)
Input voltage range±25%
Input frequency50Hz / 60Hz ±10%
Input power factor>0.95 (depending on configuration)
Output phase1P2W or 3P3W (3P4W)
Output voltage 3-phase: AC 380V / 400V / 415V / 480V (3P3W or 3P4W)
1-phase: AC 220V / 230V / 240V / 277V (1P2W)
Other specifications available
Voltage regulation±1%
Output frequency50Hz / 60Hz ±0.1%
Output power factor0.8
THDLinear load <2% · Non-linear load <3%
Crest ratio3:1
Efficiency (100% load)≥93%
RectifierIGBT rectifier with PFC (option: 6-pulse or 12-pulse phase controlled rectifier)
Inverter3-phase independent full-bridge IGBT inverter
BypassStatic bypass components
ControlDouble independent large-scale DSP control components
Overload capacity<110%: 60 min · 125%: 10 min · 150%: 1 min · 200%: 10 sec
DC input voltage (options)DC 348V / DC 220V / DC 110V
Battery input voltage (options)DC 348V / DC 384V / DC 220V / DC 125V / DC 110V (other specs available)
Cold start (without AC source)Yes
Shell protection levelIP20 (other IP protection levels available)
Max ambient temperature @ 100% load40°C continuous · 50°C less than 8 hours
Relative humidity<90% non-condensing
Altitude<1000 m above sea level
Communication interfaceDry Contact · RS232 · RS485 (MODBUS)
Minimum order85